Main
Range
PowerLogic
name of the device
PM8243
type of product or equipment
Measurement unit
Product Name
PowerLogic PM8000
service communication
SMTP e-mail notification
DHCP
Support RSTP
Synchronisation du temps NTP
Temps de synchronisation PTP
services web
Custom homepage
File upload/download via FTP File
upload/download via SFTP
Web server
Alarm notification via e-mail
View captured waveform (FTP)
View captured waveform (web )
HTTPS Server
Complementary
power quality analysis
conforming to EN 50160: 2010 conformance report conforming
to IEEE 519: 2014 conformance report conforming
to IEC 61000-4-30: class S power quality measurement
up to 63rd harmonic harmonic
distortion power
capture waveform
detection of voltage sags and swells
programmability (logic and mathematical functions)
conforming to IEC 62586 power quality monitoring
[in] rated current
1 A
10 A
5 A
application
WAGES metering Power
monitoring
facility category
III
memory capacity
512 MB
Handle front plate colour
90,5 mm
accuracy class
Class 0.2S active energy conforming to IEC 62053-22
Class 0.2 active energy conforming to ANSI C12.20
Class 0.2 active power conforming to IEC 61557-12
Class 0.5S reactive energy conforming to IEC 62053 -24
Class 0.5 power factor conforming to IEC 61557-12
Class 0.2 voltage conforming to IEC 61557-12
Class 0.2 current conforming to IEC 61557-12
data logging
Harmonic Logs
Sag and Rise Logs
GPS Sync
Timestamp
Data Reports
Trend/Forecast
Waveform
Logs Alarm Logs
Event Record Sequence
Min/Max Number of Instantaneous Values
Event Reports
product weight
528 g
measuring current
50…10000 mA
mode d'installation
snap-on
power consumed in va
18 VA at 415 V AC
security building
CAT III, 400...690 V conforming to IEC 61010-1:ed. 3
CAT III, 400...690 V conforming to EN 61010-1:ed. 3
CAT III, 347...600 V conforming to UL 61010-1:ed. 3
CAT III, 347...600 V conforming to CSA C22.2 No 61010-1:ed. 3
type of measurement
Current
Voltage
Frequency
Total active and reactive power Total
apparent
power Total power factor
Active and reactive power per phase, rms
Apparent power per phase, rms Power
factor per phase, rms
cybersecurity
Password protection
Communication port hardening
Enable/disable communication ports
Robust security logs
Syslog protocol support
information displayed
Voltage
Current
Frequency
Power Power
Consumption
Harmonic Distortion
width (w)
90,5 mm
network frequency
50 Hz
60 Hz
number of entries
3 digital 30 V AC
3 digital 60 V DC
number of outputs
1 pulse
frequency measurement range
42…69 Hz
measurement accuracy
Current +/- 0.1%
Voltage +/- 0.1%
Active energy +/- 0.2%
communication port protocol
Modbus RTU at 115 kbauds - 2 wires
ION at 115 kbauds - 2 wires
DNP3
IEC 61850
Modbus TCP/IP
Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s
RSTP 801.1d 2004
type of communication network
IPv6 (Internet protocol)
depth
90,8 mm
mounting bracket
DIN rail
support port de communication
Ethernet
Screw terminal block: RS485
sampling rate
256 samples/cycle
measuring voltage
57…400 V CA 42…69 Hz entre phase and neutre
100…690 V CA 42…69 Hz entre phases
type of display
Without display
supply voltage
90...415 V AC 45...65 Hz +/- 10%
110 à 415 V DC +/- 10%
Poles description
1P + N
3P + N
3P
analog input type
voltage (impedance 5 MOhm)
current (impedance 0.3 mOhm)
Environment
ip degree of protection
IP30 conforming to IEC 60529
operating altitude
3000 m
product certificates
CE HEAVY
N998
electromagnetic compatibility
Electrostatic discharge conforming to IEC 6100-4-11 Radiated
radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Electrical fast transient immunity test conforming to IEC
61000-4-4 surge immunity conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Power frequency magnetic field conforming to IEC 61000-4-8
Dip immunity test and voltage interruptions conforming to IEC 61000-4-11
Impulse wave immunity conforming to IEC 61000-4-12
Conducted and radiated emissions conforming to EN 55022
Conducted and radiated emissions conforming to EN 55011
Conducted and radiated emissions conforming to FCC Part 15
Conducted and radiated emissions conforming to ICES-003
Conducted RF disturbances (2...150Hz) conforming to CLC/ TR 50579
Resistance conforming to IEEE C37.90.1
standards
CEI 61557-12 CEI
62052-11
CEI 62053-22
CEI 62053-24
IEEE 1588
CEI 62586-2
CEI 61326-1
relative humidity
5…95%
operating temperature
-25…70 °C
storage room temperature
-40…85 °C