Default
Seeria
PowerLogic PM5000
Main
Range
PowerLogic
name of the device
PM5320
type of product or equipment
Measurement unit
Product Name
PowerLogic PM5000
Complementary
power quality analysis
up to 31st harmonic
[in] rated current
1 A
5 A
application
Multi-tariff
Power monitoring
maximum power consumption in va
11VA at 415V
memory capacity
256 kB
Handle front plate colour
96 mm
accuracy class
Class 0.5S active energy conforming to IEC 62053-22
data logging
Maintenance
logs Alarm
logs Min/max number of instantaneous values
Event reports
Timestamp
Data reports
product weight
430 g
measuring current
5…8500 mA
mode d'installation
Suspended
type of measurement
Current
Voltage
Frequency Power
factor
Energy
Active and reactive power
connection mode
Voltage circuit: screw terminal block4
Remote control: screw terminal block2 Current
transformer: screw terminal block6
Input/output circuit: screw terminal block6
Relay output: screw terminal block4
Ethernet network: RJ45 connector
information displayed
Fares (4)
width (w)
96 mm
network frequency
50 Hz
60 Hz
number of entries
2 digital
number of outputs
2 logic
frequency measurement range
45…65 Hz
measurement accuracy
Active energy +/- 0.5%
Reactive energy +/- 2%
Active power +/- 0.5%
Apparent power +/- 0.5%
Frequency +/- 0.05%
Power factor +/- 0.5
Current +/- 0.5%
Voltage +/- 0.5%
Apparent energy +/- 0.5%
Reactive power +/- 2%
communication port protocol
Modbus TCP/IP à 10/100 Mbit/s, isolation 2500 V
BACnet IP
depth
72 mm
mounting bracket
framework
Network type
1P + N
3P + N
3P
support port de communication
Ethernet
sampling rate
64 samples/cycle
display resolution
128 x 128 pixels
measuring voltage
35…760 V CA 45...65 Hz entre phases
20…440 V CA 45...65 Hz entre phase and neutre
type of display
Monochrome graphic LCD
supply voltage
90...450 V CA 45...65 Hz
100…300 V CC
travel time
80 ms 120 V AC typical
100 ms 230 V AC typical
100 ms 415 V AC typical
50 ms 125 V DC typical
analog input type
voltage (impedance 5 MOhm)
current (impedance <= 0.3 mOhm)
Environment
degree of pollution
2
ip degree of protection
IP54 Display: conforming to IEC 60529
IP30 rear: conforming to IEC 60529
operating altitude
2000 m CAT III
3000 m CAT II
product certificates
CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
electromagnetic compatibility
Limitation to voltage sags and jumps class A conforming to IEC 61000-3-3
Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 6100-4-11 Radiated
radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient immunity test level 4 conforming to IEC 61000-4-4
Surge immunity test level 4 conforming to IEC 61000-4-5
Dips and interruptions immunity test voltage conforming to IEC 61000-4-11
Class A harmonic current emission limitation conforming to IEC 61000-3-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Power frequency magnetic field level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
Voltage sags and sags conforming to IEC 61000-3-3
Immunity test to radiated radio-frequency electromagnetic fields conforming to IEC 61000-4-3
standards
CEI 62053-22
EN 50470-1
CEI 60529
CEI 61557-12
UL 61010-1
EN 50470-3
CEI 62053-24
relative humidity
5…95 % at 50 °C non-condensing
operating temperature
-25…70 °C counter
-20…70 °C Display
-25…-20 °C (with reduced performance) Display
storage room temperature
-40…85 °C