Additional Information
curve
C
Main
Range
Acti9
sectioning ability
No conforming to IEC 60947-1
name of the device
iC60 RCBO
type of product or equipment
Differential circuit breaker
differential sensitivity
30 mA
Product Name
Acti9 iC60 RCBO
[ui] rated insulation voltage
500V AC 50Hz
number of poles protected
2
type of trigger
Thermal-magnetic
Complementary
"no" connection
9 mm between poles
9 mm pitches
4
[ue] rated operational voltage
220...240V AC 50Hz
application
Distribution
peak current
250 A
[ics] rated service breaking capacity
7500 A 75 % Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
7.5 kA 50 % Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947 -2
Handle front plate colour
86 mm
tightening torque
2 N.m
[uimp] rated impulse withstand voltage
4 kV
compatibility of distributors, combs, busbars
Top or bottom: yes
Bottom: biconnect
in rated operational current
16 A
limiting class
3 conforming to EN/IEC 61009-2-1
product weight
273 g
fully apparent cut
Non
mode d'installation
snap-on
electrical life
10000 cycle
connection mode
Tunnel type terminal top or bottom1…35 mm² rigid Tunnel
type terminal top or bottom1…25 mm² flexible Tunnel
type terminal top or bottom1…25 mm² flexible with ferrule
mechanical endurance
20000 cycle
width (w)
36 mm
network frequency
50 Hz
Colour
Blanc
delay
Snap
voltage indication
On, off, trip on fault
position of the switchgear in the installation
Departure
wire stripping length
12mm for top or bottom connection
depth
78 mm
differential technology
Voltage independent
mounting bracket
DIN rail
magnetic trip limit
5,,,10 x In
Network type
Type AC
differential protection
Integrated
order type
Just a little bit
Poles description
2P
Environment
ip degree of protection
IP40 (distribution box) conforming to IEC 60529
IP20 conforming to IEC 60529
electromagnetic compatibility
Wave withstand 8/20 µs, 250 A conforming to EN/IEC 61009-2-1
overvoltage category
III conforming to IEC 60364
standards
EN/CEI 60947-2
EN/CEI 61009-2-1
quality labels
VDE
CHEMISTRY
IMQ
NF
relative humidity
95% at 55°C
operating temperature
-25…40 °C
storage room temperature
-40…70 °C
tropicalization
2