Main
composition of signaling contacts
2 OF contacts sans tension
product range
Acti9
name of the device
ARA iC60
type of product or equipment
Automatic reclosing auxiliary
[ui] rated insulation voltage
400V
Complementary
9 mm pitches
7
product compatibility
4P iC60
3P iC60
[un] rated nominal voltage
230 V AC 50/60Hz
range compatibility
Acti 9 (Acti9 iC60)
response time
< 500 ms
Handle front plate colour
93 mm
pulse duration
>= 200 ms remote control
tightening torque
1 Nm supply:
1 Nm input:
0.7 Nm output:
[uimp] rated impulse withstand voltage
6 kV
compatibility of distributors, combs, busbars
Non
product weight
470 g
mode d'installation
snap-on
electrical life
5000 cycle
input current
5 mA
width (w)
63 mm
Colour
Blanc
Local signalling
Flash orange LED: not operational
Flash green LED: normal operation
Flash red LED: autoreclose cycle in progress
Steady red LED: autoreclose locked
setting
Program 1: 1 reclosing, short cycle <10 s before closing /6 min verification time
Program 2: 3 reclosings, short cycle <10 s before closing /2 min verification time
Program 2: 3 reclosings, short cycle <1 min before closing /6 min checking time
Program 2: 3 reclosings, short cycle <3 min before closing /6 min checking time
Program 3: 5 reclosings, fixed long cycle <10 s before closing /2 min checking time
Program 3: 5 reclosing, fixed long cycle <1 min before closing /6 min checking time
Program 3: 5 reclosing, fixed long cycle <3 min before closing /6 min checking time
Program 4: 5 reclosing, long progressive cycle <10 s before closing /2 min verification time
Program 4: 5 reclosing, long progressive cycle <1 min before closing /6 min verification time
Program 4: 5 reclosing, long progressive cycle <3 min before closing /8 min verification time
Program 4: 5 re-closing, long progressive cycle <4 min before closing /10 min verification time
Program 4: 5 re-closing, long progressive cycle <5 min before closing /12 min verification time
wire stripping length
10 mm for bottom power supply connection:
10 mm for bottom input connection:
8 mm for top output connection:
power consumed in w
2W
depth
75,5 mm
mounting bracket
DIN rail
signaling circuit voltage
24 V 10 mA AC/DC
230 V 1 A AC
lockdown forecast
Cadenassable
order type
Inhibition of maintained automation 230 V AC 50/60 Hz
Final impulse reclosing 230 V AC 50/60 Hz
Environment
degree of pollution
3 conforming to IEC 60947
ip degree of protection
IP20 conforming to CEI 60529
overvoltage category
II
relative humidity
93% at 40°C
operating ambient air temperature
-25…60 °C
storage room temperature
-40…70 °C
tropicalization
2