Additional Information
curve
D
Main
Range
Acti9
sectioning ability
Yes conforming to EN/IEC 60947-2
name of the device
iDT40N
type of product or equipment
miniature circuit breaker
Product Name
Acti9 iDT40
[ui] rated insulation voltage
400 V AC 50 Hz conforming to EN/IEC 60947-2
number of poles protected
1
neutral pole position
Left
type of trigger
Thermal-magnetic
Complementary
9 mm pitches
2
[ue] rated operational voltage
230V AC 50Hz
application
Distribution
[ics] rated service breaking capacity
6000 A 100 % Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1
5 kA 50 % Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2
locking position
Everything
Handle front plate colour
85 mm
tightening torque
2 Nm top or bottom
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-2
in rated operational current
40 A
product weight
120 g
fully apparent cut
Yes
mode d'installation
snap-on
electrical life
10000 cycle
connection mode
Tunnel type terminal top or bottom1...10 mm² flexible Tunnel
type terminal top or bottom1...16 mm² rigid
mechanical endurance
20000 cycle
width (w)
18 mm
network frequency
50 Hz
Colour
Blanc
voltage indication
Indication ON/OFF
upstream connection
Notice
wire stripping length
14mm for top or bottom connection
depth
74 mm
mounting bracket
DIN rail
magnetic trip limit
10...14 x In conforming to EN/IEC 60898-1
12 x In +/- 20 % conforming to EN/IEC 60947-2
Network type
THAT
optional locks
Padlocking device
differential protection
separate block
order type
Just a little bit
Poles description
1P + N
Environment
degree of pollution
3 conforming to EN/IEC 60947-2
ip degree of protection
IP20 conforming to CEI 60529
IP40 (modular housing) conforming to CEI 60529
operating altitude
2000 m
product certificates
CE
BV
RINA
DNV
standards
EN/CEI 60898-1
EN/CEI 60947-2
quality labels
NF
relative humidity
95% at 55°C
operating temperature
-25…70 °C
storage room temperature
-40…85 °C