Complementary
electrical composition code
C1 (quantity <= 9)
C2 (quantity <= 7)
C3 (quantity <= 6)
C4 (quantity <= 4)
C5 (quantity <= 5)
C6 (quantity <= 3)
C7 (quantity <= 4)
C8 (quantity <= 2)
C9 (quantity <= 3)
C12 (quantity <= 6)
M1 (quantity <= 6)
M2 (quantity <= 4)
M3 (quantity <= 4)
M5 (quantity <= 2)
M6 ( quantity <= 2)
M7 (quantity <= 6)
M8 (quantity <= 4)
M9 (quantity <= 2)
SF1 (quantity <= 3)
SF2 (quantity <= 2)
MF1 (quantity <= 2)
MF2 (quantity <= 2)
C10 (quantity <= 2)
M4 (quantity <= 2)
C13 (quantity <= 1)
[ie] rated operational current
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
[ith] conventional thermal current
10 A conforming to EN/IEC 60947-5-1
assembly of the block
Front mounting
tightening torque
0.8...1.2 Nm conforming to EN 60947-1
[uimp] rated impulse withstand voltage
6 kV conforming to EN 60947-1
product weight
0,011 kg
actuation stroke
2.6 mm (electrical state modified by "F")
4.3 mm (total stroke)
electrical life
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0, 5 conforming to EN/IEC 60947-5-1 appendix C
connection mode
Screw clamp terminals, <= 2 x 1.5mm² with cable end conforming to EN 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN 60947-1
contact operation
Slow-action
contact material
Silver alloy (Ag/Ni)
mechanical endurance
10000000 cycle
actuation force
2.3 N electrical state modified by "F"
screw head shape
Crosswise compatible with pozidriv n°1 screwdriver
Perforated compatible with flat Ø 4 mm screwdriver
Perforated compatible with flat Ø 5.5 mm screwdriver
product presentation
basic element
positive aperture
Without
use of contacts
Contacts standards
type and composition of contacts
1 "F"
short circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Environment
ip degree of protection
IP20 conforming to IEC 60529
product certificates
CCC
UL
DNV
GL
GOST
LROS (Lloyds register of shipping)
BV
CSA
standards
CSA C22.2 No 14
EN/CEI 60947-5-1
UL 508
EN/CEI 60947-1
JIS C8201-5-1
EN/CEI 60947-5-4
JIS C8201-1
operating ambient air temperature
-40…70 °C
storage room temperature
-40…70 °C
mechanical shock resistance
30 gn (duration = 18 ms) for acceleration on 1/2 sinusoid conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for acceleration on 1/2 sinusoid conforming to IEC 60068-2-27
vibration resistance
5 gn (f= 2...500 Hz) conforming to IEC 60068-2-6
protective treatment
TH