Complementary
lamp base
All LEDs
[ie] rated operational current
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
[un] rated nominal voltage
230...240 V AC at 50/60 Hz
power consumption
14 mA
[ith] conventional thermal current
10 A conforming to EN/IEC 60947-5-1
contact description
1 "O" + 1 "F"
Handle front plate colour
47 mm
mounting diameter
22 mm
tightening torque
0.8...1.2 Nm conforming to EN 60947-1
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
product weight
0,097 kg
actuation stroke
1.5 mm (electrical state modified by "O")
2.6 mm (electrical state modified by "F")
4.3 mm (total stroke)
description of iso n°1 terminals
(13-14)NO
(21-22)NC
signaling unit head shape
round
bezel material
Chrome plated metal
electrical life
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0, 5 conforming to EN/IEC 60947-5-1 appendix C
resistance to high pressure cleaning
7000000Pa at 55°C, distance: 0.1m
connection mode
Screw clamp terminals, <= 2 x 1.5mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end conforming to EN/IEC 60947-1
contact operation
Slow-action
lifetime
100000 H at rated voltage and 25°C
contact material
Silver alloy (Ag/Ni)
mechanical endurance
10000000 cycle
width (w)
30 mm
electrical reliability
Λ < 10exp(-6) at 5 V and 1 mA in healthy environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V and 5 mA in healthy environment conforming to EN/IEC 60947 -5-4
supply voltage limits
195…264 V CA
actuation force
3.5 N electrical state modified by "O"
3.8 N
control unit profile
flush green
screw head shape
Transversal compatible with Phillips n° 1 screwdriver
Transversal compatible with pozidriv n°1 screwdriver
Perforated compatible with flat Ø 4 mm screwdriver
Perforated compatible with flat Ø 5.5 mm screwdriver
product presentation
Complete product
additional control unit info
With normal lens
depth
57 mm
resistance to shock waves
1 kV conforming to IEC 61000-4-5
positive aperture
With conforming to EN/IEC 60947-5-1 appendix K
use of contacts
Contacts standards
short circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
light source
Universal LED
Environment
ip degree of protection
IP66 conforming to CEI 60529
IP67
IP69
IP69K
product certificates
BV
LROS (Lloyds register of shipping)
DNV
GL
listé UL
CSA
class of protection against electric shock
Class I conforming to IEC 60536
standards
UL 508
EN/CEI 60947-5-1
CSA C22.2 No 14
EN/CEI 60947-1
EN/CEI 60947-5-5
JIS C8201-5-1
EN/CEI 60947-5-4
JIS C8201-1
shock resistance ik
IK06 conforming to IEC 50102
operating ambient air temperature
-40…70 °C
storage room temperature
-40…70 °C
mechanical shock resistance
30 gn (duration = 18 ms) for acceleration on 1/2 sinusoid conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for acceleration on 1/2 sinusoid conforming to IEC 60068-2-27
electromagnetic emission
Class B conforming to IEC 55011
vibration resistance
5 gn (f= 2...500 Hz) conforming to IEC 60068-2-6
resistance to nema environment
NO 13
NO 4X
resistance to radiated electromagnetic fields
10 V/m conforming to IEC 61000-4-3
protective treatment
TH
resistance to electrostatic discharges
6 kV on contact (metal parts) conforming to IEC 6100-4-11
8 kV free air (in insulating parts) conforming to IEC 6100-4-11
resistance to fast transients
2 kV conforming to IEC 61000-4-4