Default
Seeria
Harmony RE/RM
Main
product range
Harmony Control Relay
product specific application
For three-phase supply
switching capacity in va
1250 VA
job category
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC- 12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
type of product or equipment
3-phase control relay
rated output current
5 A
relay name
RM35TF
[ui] rated insulation voltage
400 V conforming to IEC 60664-1
parameters monitored by the relay
Undervoltage and overvoltage in window mode
Phase sequence
Detection of phase faults
Asymmetry
measuring range
220...480 V tension CA
voltage and type of control circuit
220...480V
type of relay
Multifunctional control relay
Complementary
threshold adjustment asymmetry
5 to 15% of Un selected
contact description
2 "O/F"
maximum switching current
5 A CA
5 A CC
response time
< 200 ms (in the event of a fault)
output contacts
2 "OF"
tightening torque
0.6...1 Nm conforming to IEC 60947-1
case material
Self-extinguishing plastic
minimum switching current
10 mA at 5 V DC
product weight
0,13 kg
marking
THIS
power consumed in va
0…22 VA at 400 V AC 50 Hz
reset time
1500ms at 480V
hysteresis
2,00%
connection mode
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with mouthpiece
safety reliability data
MTTFd = 399.5 years
B10d = 360000
control circuit voltage range
- 12 % + 10 % And
maximum measuring cycle
140 ms measurement cycle as actual rms value
mechanical endurance
30000000 cycle
width (w)
35 mm
control circuit frequency
50...60 Hz +/- 10 %
power frequency
50/60 Hz +/- 10 %
power-on delay
650 ms
supply voltage limits
194…528 V CA, 3 phases
delay
Adjustable 0.1…10 s, +/-10% of full scale value
Local signalling
for power ON LED (green)
for relay on LED (yellow)
for error LED (yellow)
measurement error
< 1% over the entire range with voltage variation
0.05%/°C with temperature variation
measurement voltage limits
176…528 V CA
mounting bracket
35 mm symmetrical DIN rail conforming to EN/IEC 60715
electrical stamina
100000 cycle
repeat accuracy
0.3% for time delay
0.5% for measurement and input circuit
mounting position
All positions without derating
voltage detection threshold
< 194V
voltage range of use
220 to 480 V phase-phase
command speed
<= 360 operations/hour full load
threshold setting voltage
-20...-2% in the range 380...480 V AC
2...20% of selected Un
-12...-2% in the range 220 V AC
+2...+20% in the range 220...440 V AC
+ 2 to +10% in the range of 480 V AC
maximum cut-off voltage
250 V CA
250 V CC
Environment
degree of pollution
3 conforming to IEC 60664-1
ip degree of protection
IP20 conforming to IEC 60529 (terminals)
IP30 conforming to IEC 60529 (sheath)
product certificates
GL
UL
CSA
GOST
C-Tick
electromagnetic compatibility
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential/commercial/light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to EN /IEC 61000-6-2
overvoltage category
III conforming to IEC 60664-1
standards
EN/CEI 60255-1
relative humidity
95 % at 55 °C conforming to IEC 60068-2-30
operating temperature
-20…50 °C
storage room temperature
-40…70 °C
mechanical shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
where of non-dissipative shock
4 kV
European regulation
89/336/EEC - electromagnetic compatibility
73/23/EEC - low voltage directive
vibration resistance
0.35 mm (f= 5...57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6...150 Hz) conforming to IEC 60255-21-1
dielectric test voltage
2 kV AC 50 Hz, 1 min
insulation resistance
> 500 MΩ at 500 V DC conforming to IEC 60255-5
> 500 MΩ at 500 V DC conforming to IEC 60664-1