Default
Seeria
Harmony RE/RM
Main
product range
Harmony Control Relay
switching capacity in va
1250 VA
job category
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC- 12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
type of product or equipment
Level control relay
rated output current
5 A
relay name
RM35L
[ui] rated insulation voltage
250 V conforming to IEC 60664-1
parameters monitored by the relay
Detection by resistive probes
measuring range
250 Ohm...1 MOhm
type of relay
Level control relay
Complementary
[un] rated nominal voltage
24…240 V CA/CC 50/60 Hz +/- 10 %
cable capacity
1 nF at HS (High Sensitivity) for probe cable
2.2 nF at St (normal sensitivity) for probe cable
4.7 nF at LS (low sensitivity)
contact description
2 "O/F"
maximum switching current
5 A CA/CC
output contacts
2 "OF"
tightening torque
0.6...1 Nm conforming to IEC 60947-1
case material
Self-extinguishing plastic
energy consumption
5 VA CA
minimum switching current
10 mA at 5 V DC
marking
EC : 73/23/EEC
EC : CEM 89/336/EEC
reset time
1750 ms
maximum supply current of detectors
1 mA
connection mode
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with mouthpiece
safety reliability data
B10d = 170000
MTTFd = 182.6 years
mechanical endurance
30000000 cycle
width (w)
35 mm
immunity to micro cuts
100 ms CC
90 ms CA
power-on delay
0,6 s
sensitivity scale
0.25...5 kOhm LS (low sensitivity)
5...100 kOhm St (normal sensitivity)
50...1000 kOhm HS (High Sensitivity)
supply voltage limits
20,4…264 V CA/CC
delay
Adjustable 0.1…5s, +/- 10%
Local signalling
for relay on LED (yellow)
for power ON LED (green)
for stopwatch on LED (yellow)
measurement error
0.5%/°C with temperature variation
measurement accuracy
+/-10% of full scale value
+/- 20% for HS range
mounting bracket
35 mm symmetrical DIN rail conforming to EN/IEC 60715
electrical stamina
100000 cycle
repeat accuracy
+/- 2% for time delay
mounting position
All positions without derating
sensitivity adjustment
5…100%
command speed
<= 360 operations/hour full load
operating voltage tolerance
- 15 % + 10 % And
maximum cut-off voltage
250 V CA/CC
Environment
degree of pollution
3 conforming to IEC 60664-1
ip degree of protection
IP20 conforming to IEC 60529 (terminals)
IP30 conforming to IEC 60529 (sheath)
product certificates
CSA
GL
UL
C-Tick
GOST
electromagnetic compatibility
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential/commercial/light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
overvoltage category
III conforming to IEC 60664-1
standards
EN/CEI 60255-6
relative humidity
95 % at 55 °C conforming to IEC 60068-2-30
operating temperature
-20…50 °C
storage room temperature
-40…70 °C
dielectric test voltage
2 kV AC 50 Hz, 1 min conforming to IEC 60255-5
2 kV AC 50 Hz, 1 min conforming to IEC 60664-1
insulation resistance
> 500 MΩ at 500 V DC between power supply and relay output conforming to IEC 60255-5
> 500 MΩ at 500 V DC between measurement and relay output conforming to IEC 60664-1
> 1 MOhm at 500 V DC between power supply and measurement se conforming to IEC 60255-5
> 500 MΩ at 500 V DC between power supply and relay output conforming to IEC 60664-1
> 500 MΩ at 500 V DC between measurement and relay output conforming to IEC 60255-5
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1