Default
Seeria
Harmony RE/RM
Main
product range
Harmony Control Relay
product specific application
For three-phase supply
switching capacity in va
1250 VA
job category
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC- 12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
type of product or equipment
3-phase control relay
rated output current
5 A
relay name
RM17TE
[ui] rated insulation voltage
400 V conforming to IEC 60664-1
parameters monitored by the relay
Undervoltage and overvoltage in window mode
Asymmetry
Phase sequence
Detection of phase faults
measuring range
208...480V tension CA
voltage and type of control circuit
208...480V
type of relay
Multifunctional control relay
Complementary
threshold adjustment asymmetry
5 to 15% of Un selected
contact description
1 F/O
maximum switching current
5 A CA
5 A CC
response time
< 200 ms (in the event of a fault)
output contacts
1 F/O
tightening torque
0.6...1 Nm conforming to IEC 60947-1
case material
Self-extinguishing plastic
minimum switching current
10 mA at 5 V DC
product weight
0,13 kg
marking
THIS
power consumed in va
0…22 VA at 400 V AC 50 Hz
reset time
1500 ms delay
hysteresis
2,00%
connection mode
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with mouthpiece
safety reliability data
MTTFd = 502.2 years
B10d = 470000
control circuit voltage range
- 12 % + 10 % And
maximum measuring cycle
150 ms measurement cycle as real rms value
mechanical endurance
30000000 cycle
width (w)
17,5 mm
control circuit frequency
50...60 Hz +/- 10 %
power frequency
50/60 Hz +/- 10 %
power-on delay
650 ms
supply voltage limits
183…528 V CA
delay
Adjustable 0.1…10 s, +/-10% of full scale value
Local signalling
for power ON LED (green)
for relay on LED (yellow)
measurement error
< 0.05%/°C with temperature variation
< 1% over the entire range with voltage variation
measurement voltage limits
183…528 V CA
mounting bracket
35 mm symmetrical DIN rail conforming to EN/IEC 60715
electrical stamina
100000 cycle
repeat accuracy
0.5% for measurement and input circuit
3% for time delay
sensitivity to phase loss
0.7 And
mounting position
All positions without derating
voltage range of use
208 to 480 V phase-phase
command speed
<= 360 operations/hour full load
threshold setting voltage
-2 to -17% in the range of 220 V AC
+2 to +17% in the range of 480 V AC
-2 to -12% in the range of 208 V AC
2 to 20% of Un selected
maximum cut-off voltage
250 V CA
250 V CC
Environment
degree of pollution
3 conforming to IEC 60664-1
ip degree of protection
IP20 conforming to IEC 60529 (terminals)
IP30 conforming to IEC 60529 (sheath)
product certificates
GOST
C-Tick
CSA
UL
GL
electromagnetic compatibility
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential/commercial/light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to EN /IEC 61000-6-2
overvoltage category
III conforming to IEC 60664-1
standards
EN/CEI 60255-1
relative humidity
95 % at 55 °C conforming to IEC 60068-2-30
operating temperature
-20…50 °C
storage room temperature
-40…70 °C
mechanical shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
where of non-dissipative shock
4 kV conforming to IEC 60255-5
4 kV conforming to IEC 60664-1
4 kV conforming to IEC 61000-4-5
European regulation
89/336/EEC - electromagnetic compatibility
73/23/EEC - low voltage directive
vibration resistance
0.35 mm (f= 5...57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6...150 Hz) conforming to IEC 60255-21-1
dielectric test voltage
2 kV AC 50 Hz, 1 min conforming to IEC 60255-5
2 kV AC 50 Hz, 1 min conforming to IEC 60664-1
insulation resistance
> 500 MΩ at 500 V DC conforming to IEC 60255-5
> 500 MΩ at 500 V DC conforming to IEC 60664-1