Default
Seeria
TeSyS juhtreleed
Main
Range
TeSys
[uc] control circuit voltage
48 V CC
job category
AC-15
DC-13
name of the device
CA3K
switch application
Remote
type of product or equipment
Changeover relay for VMC
composition of the poles
4F
Product Name
TeSys CAK
[ui] rated insulation voltage
690 V conforming to IEC 60947
750 V conforming to VDE 0110 gr C
690 V conforming to BS 5424
600 V conforming to CSA C22.2 No 14
control circuit type
CC standard
Complementary
[ue] rated operational voltage
<= 690 V <= 400 Hz
[ith] conventional thermal current
10A at <50°C)
caliber of the fuse to be associated
10 A gG conforming to IEC 60947
10 A gG conforming to VDE 0660
average consumption on hold in w
3W at 20°C
Handle front plate colour
58 mm
tightening torque
1.3 Nm - on screw-clamp terminals - with flat screwdriver Ø 6 mm
1.3 Nm - on screw-clamp terminals - with Phillips screwdriver no. 26 mm
1.3 Nm - on screw-clamp terminals - with pozidriv n°2 screwdriver
minimum switching current
5 mA
product weight
0,225 kg
non-overlapping distance
0,5 mm
connection mode
Screw clamp terminals 1 cable(s) 1.5...4 mm²rigid
Screw clamp terminals 2 cable(s) 1.5...4 mm²rigid
Screw clamp terminals 1 cable(s) 0.75...4 mm²flexible with end cable
length Screw clamp terminals 2 cable(s) 0.75...4 mm²flexible without cable end Screw clamp terminals
1 cable(s) 0.34...1.5 mm²flexible with cable end Screw clamp terminals
2 cable(s) 0.34...1.5 mm² flexible without cable end
control circuit voltage range
Operational: 0.8…1.15 Uc (at <50°C)
Level loss: 0.1…0.75 Uc (at <50°C)
mechanical endurance
20 Mcycles
width (w)
45 mm
immunity to micro cuts
2 ms
mechanical robustness
Contactor open vibrations: 2 Gn, 5 to 300 Hz conforming to IEC 60068-2-6
Contactor closed vibrations: 4 Gn, 5 to 300 Hz conforming to IEC 60068-2-6
Contactor open shocks: 10 Gn for 11 ms se conforming to IEC 60068-2-27
Contactor closed shocks: 15 Gn for 11 ms conforming to IEC 60068-2-27
Flame retardance
V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
rated rms inrush power
110 A conforming to IEC 60947
depth
57 mm
mounting bracket
Platine
Rail
maximum inrush power in w
3W (at 20°C)
operating time
10 ms désexcitation bobine + ouverture "F"
30…40 ms excitation bobine + fermeture "F"
max command speed
10000 cyc/h
minimum switching voltage
17V
Environment
ip degree of protection
IP2x
operating altitude
2000 m without derating
product certificates
UL
CSA
UKCA
operating ambient temperature
-25…50 °C
standards
BS 5424
CEI 60947
NF C 63-140
VDE 0660
thermal dissipation
3W
storage room temperature
-50…80 °C
protective treatment
CT conforming to IEC 60068
insulation resistance
> 10 MΩ