Default
Seeria
Harmony XALD
Main
drop box application
Two functions
housing base color
Gris clair (RAL 7035)
product range
Harmony XALD
composition of the control box
1 recessed push-button, black 1 NO, white down arrow marking
1 recessed push-button, white 1 NO, black up arrow marking
name of the device
AUNT
type of product or equipment
Complete control station
description of operators
White "up arrow" 1 F - black "down arrow" 1 F
[ui] rated insulation voltage
600 V (pollution degree 3) conforming to EN/IEC 60947-1
destination of the product
For XB5 Ø 22 mm control and signaling units
tracking location
Marking on push button
control device profile
2 flush buttons
Complementary
[ie] rated operational current
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
[ith] conventional thermal current
10 A conforming to EN/IEC 60947-5-1
tightening torque
0.8...1.2 Nm conforming to EN/IEC 60947-1
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
marking color
White marking with green, red or black caps Black
marking with white cap
cable entry
2 knockouts for cable entry, clamping capacity: 14 mm
2 knockouts for Pg 13 and ISO M20 cable gland, clamping capacity: 12 mm
matter
Polycarbonate
product weight
0,233 kg
actuation stroke
2.6 mm (electrical state modified by "F")
4.3 mm (total stroke)
electrical life
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0, 5 conforming to EN/IEC 60947-5-1 appendix C
resistance to high pressure cleaning
7000000Pa at 55°C, distance: 0.1m
connection mode
Screw clamp terminals, <= 2 x 1.5mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1
contact operation
Slow-action
hood color
Dark gray (RAL 7016)
contact material
Silver alloy (Ag/Ni)
mechanical endurance
10000000 cycle
electrical reliability
Λ < 10exp(-6) at 5 V and 1 mA conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V and 5 mA conforming to EN/IEC 60947-5-4
actuation force
3.8 N electrical state modified by "F"
screw head shape
Transversal compatible with Phillips n° 1 screwdriver
Transversal compatible with pozidriv n°1 screwdriver
Perforated compatible with flat Ø 4 mm screwdriver
Perforated compatible with flat Ø 5.5 mm screwdriver
positive aperture
Without
short circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Environment
ip degree of protection
IP66 conforming to CEI 60529
IP67
IP69
IP69K
class of protection against electric shock
Class II conforming to IEC 60536
standards
JIS C8201-5-1
EN/CEI 60947-1
CSA C22.2 No 14
EN/CEI 60947-5-4
EN/CEI 60947-5-1
UL 508
EN/CEI 60947-5-5
JIS C8201-1
shock resistance ik
IK03 conforming to EN 50102
operating ambient air temperature
-40…70 °C
storage room temperature
-40…70 °C
mechanical shock resistance
30 gn (duration = 18 ms) for acceleration on 1/2 sinusoid conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for acceleration on 1/2 sinusoid conforming to IEC 60068-2-27
vibration resistance
5 gn (f= 12...500 Hz) conforming to IEC 60068-2-6
resistance to nema environment
NO 13
NO 4X
protective treatment
TH