Main
product range
Modicon Safety automation
reliability data
PFHd = 6.06E-9 1/h
DC > 99%
MTTFd < 100 years high
name of the device
XPSMCM
type of product or equipment
Safety Controller Central Unit
security level
Up to category 4 conforming to EN/ISO 13849-1
Up to PL = e conforming to EN/ISO 13849-1
Type 4 conforming to EN/IEC 61496-1
SILCL 3 conforming to IEC 62061
Complementary
charge capacity
0,82 µF
[un] rated nominal voltage
24 V - 20...20 % CC
inductive load
30 mH
data storage equipment
SD card (optional)
Handle front plate colour
99 mm
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 61800-5-1
product weight
0,25 kg
logic output current
400 mA
digital input current
400 mA
connection mode
2 captive screw terminals, removable terminal block
1 captive screw terminals, removable terminal block
lifetime
20 year(s)
maxi i/o extension module name
14 with 128 discrete output(s) for input
14 with 16 discrete output(s) for output
voltage logic input
24V
width (w)
22,5 mm
function available
Emergency stop conforming to EN/ISO 13850 Guard
monitoring conforming to EN/ISO 14119
Switch monitoring activation conforming to EN/IEC 60947-5-1
Light curtain monitoring conforming to EN/IEC 61496- 1
Foot switch monitoring conforming to EN/IEC 60947-5-1
Magnetic switch monitoring conforming to EN/ISO 14119
Two-hand control conforming to EN 574
Safety mat monitoring conforming to EN/ISO 14119
Activation of monitoring by switch conforming to EN 61326-1
Muting function of light curtains conforming to EN/IEC 60947-5-1
Counter functions conforming to EN/IEC 61800-5-2
Speed monitoring conforming to EN/IEC 61800-5-2
integrated communication ports
Motherboard expansion bus
USB 2.0 port
isolation
250 V AC between power supply and housing conforming to EN/IEC 61800-5-1
number of entries
8 digital for input connection
2 digital for interlock start/restart or external device monitoring
number of outputs
2 OSSD safety outputs for contactor/drive connection
4 test for line control outputs
2 configurable for diagnostic connection
Local signalling
1 green LED with PWR marking for power ON
1 green LED with RUN marking for RUN (status)
1 red LED with E IN marking for internal error
1 red LED with E EX marking for external error
1 orange LED with COM marking for communication
1 LED blue with EN marking for master
enable 8 LEDs yellow with IN marking for input status
2 LEDs green/red with output marking for output status
2 yellow LEDs with RST marking for restart signal
2 yellow LEDs with STATUS marking for control channel exit
cable section
0.2...1.5 mm² - AWG 24...AWG 16 flexible cable without cable end
0.2...2.5 mm² - AWG 24...AWG 14 flexible cable without cable end
0.25...1 mm² - AWG 23...AWG 18 flexible cable with cable end cable, without bezel
0.25...2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, with bezel
0.25...1.5 mm² - AWG 23...AWG 16 flexible cablewith cable end, without bezel
0, 5...1.5 mm² - 4 x 1.5 mm² + 2 x 1 mm² + 2 x 0.14 mm² flexible cable with cable end, with double bezel
0.2...1 mm² - AWG 24...AWG 18 rigid cable without cable end
0 ,2…2.5 mm² - AWG 24…AWG 14 rigid cable without cable end
depth
114,5 mm
mounting bracket
Omega 35 mm DIN rail conforming to EN 50022
power dissipation in w
3W
synchro time between inputs
< 0,5 ms
electrical connection
Screw terminal block
logic input type
PNP safety input
logic output type
PNP
Environment
degree of pollution
2
ip degree of protection
IP20
product certificates
cULus
RCM
TÜV
electromagnetic compatibility
Electrostatic discharge immunity test - test level: 6 kV (with contact) conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test - test level: 20 kV (in air) conforming to EN/IEC 61000-4-2 conforming to EN/IEC 61000-4-2
Disturbance due to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to EN/IEC 61000-4-3
Disturbance due to electromagnetic fields - level test voltage: 30 V/m (1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
overvoltage category
II
standards
EN/CEI 61508
EN/ISO 13849-1
EN/CEI 61496-1
EN/CEI 61800-5-1
CEI 62061
quality labels
THIS
relative humidity
10…95%
operating ambient air temperature
-10…55 °C
storage room temperature
-20…85 °C
mechanical shock resistance
10 gn (duration = 16 ms) for 1000 shocks on each axis conforming to EN/IEC 61496-1
vibration resistance
+/-0.35 mm (f= 10...55 Hz) conforming to EN/IEC 61496-1