Main
product range
Preventa safety automation
reliability data
MTTFd = 210.4 years conforming to EN/ISO 13849-1
DC > 99 % conforming to EN/ISO 13849-1
PFHd = 3.56E-9 1/h conforming to EN/IEC 62061
[uc] control circuit voltage
24V
module function
Emergency stop Switch
monitoring
type of product or equipment
Preventa safety module
[ui] rated insulation voltage
300 V (pollution degree 2) conforming to IEC 60947-5-1
300 V (pollution degree 2) conforming to DIN VDE 0110 part 1
security level
Up to PL e/category 4 conforming to EN/ISO 13849-1
Up to SILCL 3 conforming to EN/IEC 62061
security module name
XPSAC
number of additional circuits
1 static output
start type
Not monitored
use of security module
Emergency stop and switch control
Complementary
[un] rated nominal voltage
24 V CA - 20...10 %
24 V CC - 20...20 %
power consumption
40 mA at 24 V DC at over voltage supply
90 mA at 24 V AC at over voltage supply
[ics] rated service breaking capacity
1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
[ith] conventional thermal current
10,5 A
caliber of the fuse to be associated
4 A gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
6 A fast blow for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
maximum power consumption in va
2.5 VA AC
[uimp] rated impulse withstand voltage
4 kV overvoltage category III conforming to IEC 60947-5-1
4 kV overvoltage category III conforming to DIN VDE 0110 part 1
product weight
0,16 kg
minimum output current
10 mA for relay output
output thermal current
6 A per relay for relay output
connection mode
Captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² flexible without cable end
Captive screw clamp terminals, 1 x 0.14...1 x 2.5 mm² rigid without cable end
Captive screw clamp terminals , 1 x 0.25...1 x 1.5 mm² flexible with cable end, with bezel
Captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel
Screw terminal blocks captive screw clamps, 2 x 0.14...2 x 0.75 mm² flexible without cable end
Captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² rigid without cable end
Captive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel
Captive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
power frequency
50/60 Hz
Local signalling
2 LEDs
maximum response time on opening of inputs
100 ms
minimum output voltage
16 V for relay output
mounting bracket
35 mm symmetrical DIN rail
maximum power consumption in w
1,2 W CC
type of output
Relay instantaneous opening, 3 NO circuit(s), volt free
Environment
ip degree of protection
IP20 (terminals) conforming to EN/IEC 60529
IP40 (housing) conforming to EN/IEC 60529
product certificates
UL
CSA
TÜV
standards
EN/CEI 60947-5-1
EN/ISO 13850
EN 60204-1
EN 1088/ISO 14119
operating ambient air temperature
-10…55 °C
storage room temperature
-25…85 °C