Main
Fluid connection type
G 1/4A (male) conforming to DIN 3852-E
controlled fluid
Air (-30-135 °C), fresh water (0-135 °C), hydraulic oil (-30-135 °C), gas (-30-135 °C), refrigeration fluid (-30-135 °C)
Type of packing
Individual
pressure sensor name
XMLP
pressure sensor type
Pressure transmitter
Complementary
Accuracy
0.1 % of the measuring range
local display
Without
Product certifications
CERCMcULus
Product or component type
Electronic pressure sensors
[us] rated supply voltage
5 V DC SELV (voltage limits: 4.5-5.5 V)
Analogue output function
0.5...4.5 V, 3-wire
Current consumption
< 7 mA
Quantity per set
Set of 1
Drift of the sensitivity
+/- 0,02 % of measuring range/°K
Drift of the zero point
+/- 0,02 % of measuring range/°K
Electrical circuit type
Control circuit
measurement accuracy
+/- 0,5 % de la plage de mesure
Operating position
Any position
Materials in contact with fluid
Fluorocarbon FPMstainless steel AISI 316L
electrical connection
1 male connector EN 175301-803-A (ex DIN43650) 3 pins
Shock resistance
100 gn for 11 ms conforming to IEC 60068-2-27
Response time on output
<= 2 ms 10...90 % of full scale
Type of output signal
Analogue
Protection type
Load short-circuitreverse polarity
Environment
ip degree of protection
IP65 conforming to IEC 60529
Range of product
Telemecanique Pressure sensors XM
electromagnetic compatibility
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 2 kV, electrostatic discharge immunity test conforming to IEC 61000-4-2 8 kV air, 4 kV contact, 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 1 kV 42 Ohm, immunity to magnetic fields conforming to IEC 61000-4-8 100 A/m 50 Hz, susceptibility to electromagnetic fields conforming to IEC 61000-4-3 10 V/m 80...3000 MHz, radiated RF fields conforming to IEC 61000-4-6 10 V 0.01...80 MHz
standards
IEC 61326-2-3NSF ANSI 61
vibration resistance
20 gn (f = 15-2000 Hz) conforming to IEC 60068-2-6
protective treatment
TC