Default
Seeria
TeSyS Deca GV3 mootorikaitselüliti
Main
Range
TeSys Deca
TeSys Deca
sectioning ability
Yes conforming to IEC 60947-1
job category
AC-3 conforming to IEC 60947-4-1
name of the device
GV3P
type of product or equipment
motor circuit breaker
magnetic tripping current
700 A
Product Name
TeSys GV3
TeSys Deca
motor power kW
22 kW at 400/415 V AC 50/60 Hz
30 kW at 500 V AC 50/60 Hz
45 kW at 690 V AC 50/60 Hz
type of trigger
Thermal-magnetic
Complementary
[in] rated operational current
50 A
[ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
application
Motor protection
[ics] rated service breaking capacity
100% at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100% at 440 V AC 50/60 Hz conforming to IEC 60947-2
100% at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
[ith] conventional thermal current
50 A conforming to IEC 60947-4-1
Handle front plate colour
132 mm
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
product weight
0,96 kg
electrical life
50000 cycles for AC-3 at 415 V In
mechanical endurance
50000 cycle
width (w)
55 mm
network frequency
50/60 Hz conforming to IEC 60947-4-1
assigned department
Continuous conforming to IEC 60947-4-1
depth
136 mm
Network type
THAT
sensitivity to phase loss
Yes conforming to IEC 60947-4-1
power loss per pole
8W
order type
Rotating handle
Poles description
3P
Environment
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
3000 m
product certificates
CCC
EAC
BV
LROS (Lloyds register of shipping)
DNV-GL
ABS
UL
CSA
UKCA
ATEX
standards
EN/CEI 60947-2
EN/CEI 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
fire resistance
960 °C conforming to IEC 60695-2-11
operating temperature
-20…60 °C
storage room temperature
-40…80 °C
climatic resistance
conform to IACS E10