Main
Range
TeSys
[uc] control circuit voltage
110 V CA 50...400 Hz
110 V CC
job category
AND-1
AND-3
AND-4
name of the device
CR1F
switch application
Resistive load (AC-1)
Motor control (AC-3)
type of product or equipment
Magnetic interlock switch
Product Name
TeSys F
[ui] rated insulation voltage
1000 V conforming to IEC 60158-1
1000 V conforming to IEC 60947-4
1000 V conforming to BS 775
1500 V conforming to VDE 0110 gr C
control circuit type
AC to 50...400 Hz
Standard DC
composition of the power pole contacts
3F
motor power kW
200 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0,28 mOhm - Ith 500 A 50 Hz
Complementary
average consumption
1600 VA AC 50...400 Hz latching
16 VA AC 50...400 Hz unlocking
1600 VA DC latching
16 VA DC unlocking
[ie] rated operational current
400 A (at <40°C) at <= 440 V AC AC-3
500 A (at <40°C) at <= 440 V AC AC-1
370 A (at <40°C) at <= 440 V AC AC-4
[ue] rated operational voltage
1000 V AC 25 to 200 Hz
application
Control
[ics] rated service breaking capacity
4000 A at 220...440 V
3500 A at 500 V
1200 A at 1000 V
3000 A at 660/690 V
[icw] rated short-time withstand current
3600 A at <40°C - 1s
3600 A at <40°C - 5 s
3600 A at <40°C - 10 s
2400 A at <40°C - 30 s
1700 A at <40°C - 1 min
1200 A at <40°C - 3 min
1000 A at <40°C - 10 min
caliber of the fuse to be associated
400 A aM at <= 440 V
500 A BS88 at <= 440 V
500 A gG at <= 440 V
Handle front plate colour
206 mm
tightening torque
35 N.m
product weight
9,1 kg
connection mode
Ring terminals 2 cable(s) 150 mm²
Busbars 2 cable(s) - busbar section: 30 x 5 mm
Power circuit: connection by bolting
control circuit voltage range
Latching: 0.85…1.1 Uc
Unlatching: 0.85…1.1 Uc
mechanical endurance
1 Mcycles
width (w)
213 mm
rated rms inrush power
4500 A
depth
219 mm
operating time
40…75 ms latching
50…100 ms unlocking
power loss per pole
45 W AC-3
70 W AC-1
max command speed
120 cycles/h at <40°C
Poles description
3P
Environment
operating altitude
3000 m without derating
product certificates
scheme CB
UL
CSA
EAC
CE
UKCA
operating ambient temperature
-15…70 °C
standards
EN/CEI 60947-1
EN/CEI 60947-4-1
JIS C8201-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
storage room temperature
-60…80 °C
protective treatment
TC