Main
Range
New generation ComPacT
sectioning ability
Yes conforming to EN/IEC 60947-2
job category
Category A
name of the device
NSX100HB2
type of product or equipment
Circuit breaker
Product Name
Next Generation ComPacT NSX
[ui] rated insulation voltage
800 V AC 50/60 Hz
trigger protection functions
LSIG
circuit breaker installation mode
Fixed
performance level
HB2 100 kA 690 V AC
trigger name
Micrologic 6.2 E-M
type of trigger
Electronic
ultimate short-circuit breaking capacity [icu]
100 kA Icu at 500 V AC 50/60 Hz if conforming to CEI 60947-2
100 kA Icu at 525 V AC 50/60 Hz if conforming to CEI 60947-2
100 kA Icu at 660/690 V AC 50/60 Hz if comply with IEC 60947-2
protected poles
3d
Complementary
"no" connection
35 mm
motor trip class
30
20
10
5
[in] rated operational current
25 A at 65 °C
[ue] rated operational voltage
690 V AC 50/60 Hz
application
Motor protection
[ics] rated service breaking capacity
100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
short-time protection threshold setting range [isd]
5...13 x And
Handle front plate colour
161 mm
trigger caliber
25 A at 65 °C
[uimp] rated impulse withstand voltage
8 kV
earth protection time delay setting range [tg]
0…0,4 s
product weight
2,05 kg
earth fault protection threshold setting range [ig]
0,6…1 x In
Activation Ig on/off
tsd short time protection time delay setting
Fixed
additional engine protection
Prolonged starting time
Incomplete load Stalled
rotor
Phase imbalance
electrical life
20000 cycles at 440 V In/2
10000 cycles at 440 V In
10000 cycles at 690 V In/2
5000 cycles at 690 V In
setting the differential protection time delay δt
Adjustable
type of measurement
energy meter
Data recording
Instantaneous and demand values
Phase sequence
Power quality Maintenance
indicators
Energy measurement
Protection and alarm parameters
Current and power demand
Thermal image function
Stamping time histories and event tables
Maximeters/minimeters
mechanical endurance
20000 cycle
width (w)
105 mm
network frequency
50/60 Hz
thermal memory
20 minutes before and after triggering
Local signalling
forready for operation LED flashing (green)
fortemperature higher than the set value LED 95% Ith (red)
setting the earth fault protection time delay tg
Adjustable 5 positions
long time protection time delay setting range [tr]
120 s at 1.5 x Irfor type 5
6.5 s at 6 x Irfor type 5
5 s at 7.2 x Irfor type 5
240 s at 1.5 x Irfor type 10
13.5 s at 6 x Irfor type 10
10 s at 7.2 x Irfor type 10
480 s at 1.5 x Irfor type 20
26 s at 6 x Irfor type 20
20 s at 7.2 x Irfor type 20
720 s at 1.5 x Irfor type 30
38 s at 6 x Irfor type 30
30 s at 7.2 x Irfor type 30
setting range of the long-time protection threshold [ir] (thermal protection)
12...25 A
upstream connection
Façade
downstream connection
Façade
instantaneous protection threshold setting range [ii] (short-circuit protection)
425 A
number of slots for electrical auxiliaries
5 slot(s)
ig earth fault protection sensor setting
Adjustable 9 positions
mounting bracket
back plate
depth (p)
86 mm
Network type
THAT
differential protection
Without
mounting position
Horizontal et vertical
Flat on the back
power loss per pole
0.53W
tr long time protection time delay setting
Adjustable
instantaneous protection sensor setting ii (short circuit protection)
Fixed
ir long time protection sensor setting (thermal protection)
Adjustable 9 positions
order type
Just a little bit
type of display
LCD display
kind of protection
L: for overload protection (long delay)
So: for short delay protection
I: for instantaneous short-circuit
protection G: for short-circuit to ground protection
zsi logic selective latch area
With
Poles description
3P
Environment
degree of pollution
3 conforming to IEC 60664-1
ip degree of protection
IP40 conforming to CEI 60529
operating altitude
0...2000 m without current reduction
2000 m...5000 m with current reduction
product certificates
EAC
CCC
Marine
class of protection against electric shock
Class II
operating ambient temperature
-25…70 °C
overvoltage category
Class II
standards
EN/CEI 60947
relative humidity
0…95%
shock resistance ik
IK07 conforming to IEC 62262
storage room temperature
-40…85 °C