Main
product range
ComPacT NSX100...250 new generation
Range
New generation ComPacT
type of product or equipment
Trigger
trigger protection functions
LSoI
circuit breaker installation mode
Fixed
trigger name
Micrologic 2.2 M
type of trigger
Electronic
protected poles
3d
Complementary
motor trip class
20
10
5
[ue] rated operational voltage
690 V AC 50/60 Hz
application
Engine
range compatibility
Next generation ComPacT
NSX100 Next generation ComPacT
NSX160 Next generation ComPacT NSX250
short-time protection threshold setting range [isd]
5...13 x And
trigger caliber
100 A at 65 °C
tsd short time protection time delay setting
Fixed
additional engine protection
Phase imbalance
setting the differential protection time delay δt
Adjustable 9 positions
network frequency
50/60 Hz
thermal memory
20 minutes before and after triggering
Local signalling
forready for operation LED flashing (green)
fortemperature higher than the set value LED 95% Ith (red)
long time protection time delay setting range [tr]
120 s at 1.5 x Irfor type 5
6.5 s at 6 x Irfor type 5
5 s at 7.2 x Irfor type 5
240 s at 1.5 x Irfor type 10
13.5 s at 6 x Irfor type 10
10 s at 7.2 x Irfor type 10
480 s at 1.5 x Irfor type 20
26 s at 6 x Irfor type 20
20 s at 7.2 x Irfor type 20
setting range of the long-time protection threshold [ir] (thermal protection)
50...100 A
instantaneous protection threshold setting range [ii] (short-circuit protection)
1500 A
Network type
THAT
differential protection
Without
tr long time protection time delay setting
Fixed
instantaneous protection sensor setting ii (short circuit protection)
Fixed
ir long time protection sensor setting (thermal protection)
Adjustable 9 positions
kind of protection
L: for overload protection (long delay)
So: for short delay protection with fixed delay
I: for instantaneous protection against short-circuit
zsi logic selective latch area
Without
Poles description
3P
Environment
degree of pollution
3 conforming to IEC 60947-1
ip degree of protection
IP40 conforming to CEI 60529
class of protection against electric shock
Class II
operating ambient temperature
-25…70 °C
standards
EN/CEI 60947-2
storage room temperature
-50…85 °C