Default
Seeria
Altistart 22
Main
available functions
Internal bypass
product range
Altistart 22
product specific application
Pumps and fans
[uc] control circuit voltage
230V - 15...10% 50/60Hz
job category
AC-53A
starter caliber icl
62 A for connection in the motor supply line for standard applications
type of product or equipment
Soft starter
factory setting current
57 A
destination of the product
Asynchronous motors
component name
ATS22
number of network phases
3 phases
communication protocol
Modbus
motor power kW
15 kW 230 V
30 kW 400 V
30 kW 440 V
start type
Starting with torque control (current limited to 3.5 In)
Complementary
[un] rated nominal voltage
230...440V - 15...10%
device installed
31
control circuit consumption
20W
maximum switching current
5 A 250 V AC resistive 1 relay outputs
5 A 30 V DC resistive 1 relay outputs
2 A 250 V AC inductive 0.4 20 ms relay outputs
2 A 30 V DC inductive 7 ms relay outputs
Handle front plate colour
295 mm
minimum switching current
100 mA at 12 V DC (relay outputs)
output current
0.4…1 Icl adjustable
product weight
12 kg
marking
THIS
ptc probe input
750 Ohm
width (w)
145 mm
network frequency
45…66 Hz
power frequency
50...60 Hz - 10...10 %
supply voltage limits
195…484V
physical interface
RS485 multipoint
communication computer link
Series
connector type
1 RJ45
depth
207 mm
motor power range ac - 3
15…25 kW at 200…240 V 3 phases
30…50 kW at 380…440 V 3 phases
power dissipation in w
59 W pour applications standard
logic input
Positive logic LI1, LI2, LI3 at state 0: < 5 V and <= 2 mA at state 1: > 11 V, >= 5 mA
mounting position
Vertical +/- 10 degrees
device connection
At the motor delta terminals In the motor
supply line
logic input voltage
24V<=30V
kind of protection
Phase fault: line
Thermal protection: motor
Thermal protection: starter
motor starter type
Soft starter
construction options
With heat sink
number of logic inputs
3
kind of cooling
Forced convection
number of logic outputs
2
baud rate
4800, 9600 or 19200 bps
logic input type
(LI1, LI2, LI3) logic, 5 mA 4.3 kOhm
logic output type
Relay outputs R1 230 V on, alarm, tripped, stop, run, start, ready C/
O Relay outputs R2 230 V on, alarm, tripped, stop, run, start, ready C/O
Environment
degree of pollution
Level 2 conforming to IEC 60664-1
ip degree of protection
IP20
operating altitude
<= 1000 m without derating
> 1000…< 2000 m with load reduction of 2.2% per additional 100 m
product certificates
C-Tick
CCC
UL
CSA
GOST
electromagnetic compatibility
Conducted and radiated emissions level A conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 6100-4-11
Electrical transient immunity level 4 conforming to IEC 61000-4-4
Immunity against radiated radio interference level 3 conforming to IEC 61000-4-3
Impulse voltage/current level 3 conforming to IEC 61000-4-5
standards
EN/CEI 60947-4-2
relative humidity
0...95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
operating ambient air temperature
-10…40°C (without derating)
40…60°C (with current reduction of 2.2% per degree)
storage room temperature
-25…70 °C
mechanical shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
sound pressure
45 dB
vibration resistance
1 gn (f= 13...200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f= 2...13 Hz) conforming to EN/IEC 60068-2-6