Main
product range
Modicon Transformer Universal
protection cover
With
secondary winding
Double
type of product or equipment
Safety and isolation transformer
Complementary
electrical insulation class
Class B
max voltage drop at rated load
4.23%
output coupling
Grounding of the secondary
Parallel
Series by internal jumper
Handle front plate colour
108,0 mm
product weight
2,86 kg
rated power in va
100 VA
fixing method
By 4 screws (diameter: 5.5 mm on vertical panel, operating position: horizontal
By 4 screws (diameter: 5.5 mm on vertical panel, operating position: vertical
By clips on symmetrical rail 35x15mm
By 4 screws (diameter: 5.5mm on horizontal panel with 90% load reduction
marking
THIS
network frequency limits
47…63 Hz
led status
1 LED (orange) input voltage
connection mode
for input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11
for input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11
for output connection: screw type, connection capacity: 4 x 4 mm² AWG 11
output voltage
115/230V CA
width (w)
87,0 mm
input voltage limits
360...440V
207...253V
no-load losses (without tolerance)
11.26W
sustained output overvoltage
4.90% (no load, under voltage)
depth
138,0 mm
power dissipation in w
16.3W
tension de court-circuit
6.20%
input voltage tolerance
+/- 15V
yield
86,00%
input voltage
230 V AC single-phase, connection(s): N-L1
400 V AC phase-phase, connection(s): L1-L2
voltage variation at rated load
4% at 230V
4.17% at 400V
dielectric strength
3200 V between input and ground
3200 V between output and ground
5100 V between input and output
output protection type
Against overload, protection technology: with additional protection fuses or circuit breakers in Protection selection
Against overvoltage, protection technology: with additional protection fuses or circuit breakers in Protection selection
Against short-circuits, protection technology: with additional protection fuses or circuit breakers in Protection Selection
Environment
degree of protection (ip)
IP20
environment characteristic
EMC conforming to EN 62041
Safety conforming to EN 61558-1
Safety conforming to EN 61558-2-4
operating altitude
3000 m
product certificates
UR
EAC
DNV-GL
overvoltage category
Class I conforming to VDE 0106-1
standards
UL 506
relative humidity
0…95% operation in progress
operating ambient air temperature
-20…60 °C
storage room temperature
-40…80 °C