Main
power supply module output current
6,25 A
product range
Alimentation Modicon
type of product or equipment
power supply
nominal power in w
150W
rated input voltage
100...120 V AC single phase
200...240 V AC single phase
kind of power supply
Regulated switching mode
optional variant
Panel mount
Complementary
18 mm pitches
0.55 at 115 V AC
0.45 at 230 V AC
feed
SELV conforming to EN/IEC 60950-1
SELV conforming to EN/IEC 60204-1
SELV conforming to IEC 60364-4-41
power consumption
< 3,2 A 115 V CA
< 1,9 A 230 V CA
output coupling
Parallel
Series
Handle front plate colour
30 mm
maximum leakage current
1mA 240V AC
case material
Aluminium
inrush current
35 A at 115 V
70 A at 230 V
expected capacitor life
10 year(s)
product weight
0,36 kg
starting with capacitive loads
7000 µF
led status
1 LED (green) output voltage
connection mode
Screw connection: 0.75...2.5 mm², (AWG 18...AWG 14) without cable end
Screw connection: 0.75...1.5 mm², (AWG 18...AWG 16) with ferrule cable end
nominal network frequency
50…60 Hz
output voltage
24 V CC
width (w)
97 mm
input voltage limits
90...132 VCA
170...264 VCA
line and load regulation
< 0,5 % network 0 to 100 % load at 25 °C
< 1 % network full voltage range in line at 25 °C
residual ripple
< 170 mV
depth
159 mm
mounting bracket
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
DIN double profile rail
panel mounting
power dissipation in w
29 W
yield
88.8% at 230V AC
output voltage adjustment
21.6…26.4V
compatible network system
TN
TT
IT
mataining time
> 20 ms 115 V CA
> 40 ms 230 V CA
start-up time
< 500 ms
mean time between failures (mtbf)
700000 H at 25 °C, pleine charge conforming to SR 332
dielectric strength
3750 V CA avec input to output
output protection type
Against overload and short-circuits, protection technology: automatic reset
Against overheating, protection technology: manual reset
Against overvoltage, protection technology: manual reset
input protection type
Built-in fuse (not interchangeable) 4 A
Environment
degree of pollution
2
environment characteristic
3M4 conforming to IEC 60721-3-3
ip degree of protection
IP10
operating altitude
5000 m
product certificates
CE
CULus
EAC
RCM
Schéma CB
KC
ambient air temperature for operation
-30…-25 °C with current derating of 4 % per °C mounting position B, G < 2000 m
-25…50 °C without derating mounting position B, G < 2000 m
50…70 °C with current derating of 2 % per °C mounting position B, G < 2000 m
class of protection against electric shock
Class I
standards
EN 62368-1
EN/CEI 61010-1
EN 61010-2-201
EN/CEI 61204-3
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
EN 61000-3 -2
EN 61000-3-3
UL 62368-1
UL 61010-1
UL 61010-2-201
CSA C22.2 No 62368-1
CSA C22.2 No 61010-1
CSA C22.2 No 61010-2-201
IEC 60335 -1
EN/IEC 62368-1
mechanical shock resistance
100 m/s² pour 11 ms
electromagnetic emission
Conducted emissions conforming to EN 61000-6-3
Radiated emissions conforming to EN 61000-6-4
vibration resistance
3 mm (f= 2...9 Hz) conforming to IEC 60068-2-6
10 m/s² (f= 9...200 Hz) conforming to IEC 60068-2-6
electromagnetic immunity
Immunity to electrostatic discharge - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2
Immunity to electrostatic discharge - test level: 9 kV (air discharge) conforming to EN/ IEC 61000-4-2
Immunity to conducted RF disturbances - test level: 10 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 3 V/m (2.7...6 GHz ) conforming to EN/IEC 61000-4-3
Immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4
Surge immunity test - test level: 3 kV (between supply and earth) conforming to EN/IEC 61000-4-5
Surge immunity test - test level: 1.5 kV (between phases) conforming to EN/IEC 61000-4-5
Immunity to conducted RF disturbances - test level: 10 V (0.15 to 80 MHz) conforming to EN/IEC 61000-4-6
Immunity to magnetic fields - test level test: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8
Immunity to voltage drops conforming to EN/IEC 61000-4-11
Disturbance field emission conforming to EN 55016- 2-3
Limitation of harmonic current emission conforming to EN 61000-3-2
Disturbance emission transmitted by conduction conforming to EN 55016-1-2
Conducted disturbance emission conforming to EN 55016-2-1