Additional Information
curve
D
Main
product range
C120
Range
Acti9
sectioning ability
Yes conforming to IEC 60947-2
name of the device
C120N
type of product or equipment
miniature circuit breaker
Product Name
C120
[ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
number of poles protected
2
neutral pole position
Left
type of trigger
Thermal-magnetic
Complementary
9 mm pitches
6
[ue] rated operational voltage
380...415 V AC 50/60 Hz
220...240 V AC 50/60 Hz
440 V AC 50/60 Hz
<= 250 V DC
230...400 V AC 50/60 Hz
application
Distribution
[ics] rated service breaking capacity
7500 A 75% according to EN/CEI 60898-1 - 230...400 V AC 50/60 Hz
4.5 kA 75% according to EN/CEI 60947-2 - 440 V AC 50/60 Hz
7, 5 kA 75 % according to EN/CEI 60947-2 - 380...415 V AC 50/60 Hz
15 kA 75 % according to EN/CEI 60947-2 - 220...240 V AC 50/60 Hz
10 kA 100 % conforms to EN/CEI 60947-2 - <= 250 V DC
Handle front plate colour
81 mm
tightening torque
3,5 N.m
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
compatibility of distributors, combs, busbars
Yes
in rated operational current
80 A at 30 °C
limiting class
3 conforming to EN/IEC 60947-2
product weight
0,41 kg
fully apparent cut
Yes
mode d'installation
snap-on
electrical life
5000 cycles conforming to IEC 60947-2
connection mode
Tunnel type terminal 1...50 mm² rigid
Tunnel type terminal 1.5...35 mm² flexible
magnetic trigger
10...14 x In
mechanical endurance
20000 cycle
width (w)
54 mm
network frequency
50/60 Hz
Colour
Blanc
voltage indication
Indication ON/OFF
wire stripping length
15 mm
depth
73 mm
mounting bracket
35 mm symmetrical DIN rail
Network type
THAT
differential protection
separate block
order type
Just a little bit
Poles description
2P
Environment
degree of pollution
3 conforming to IEC 60947-2
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
2000 m
product certificates
EAC
overvoltage category
IV
standards
EN/CEI 60947-2
EN/CEI 60898-1
relative humidity
95% at 55°C
operating ambient air temperature
-25…70 °C
storage room temperature
-40…85 °C
tropicalization
2 conforming to IEC 60068-1