Main
product range
Acti9
[uc] control circuit voltage
230...240 V CA 50/60 Hz
110 V CC
name of the device
iTL
type of product or equipment
Toggle switch
composition of the poles
4F
Product Name
Acti9 iTL
poles
4P
Complementary
9 mm pitches
4
[in] rated operational current
16 A
[ue] rated operational voltage
415V AC 50/60Hz
application
Standard
range compatibility
Acti 9 iATEt
Acti 9 iATL4
Acti 9 iATLc
Acti 9 iATLc+s
Acti 9 iATLm
Acti 9 iATLs
Acti 9 iATLz
Acti 9 iETL iTL 16
Acti 9 iATLc+c
Acti 9 iATL24
control signal type
Impulse
Handle front plate colour
84 mm
pulse duration
50 ms…1 s
tightening torque
1 N.m
mode d'installation
Fixed
electrical life
AC-21: 200000 cycle
AC-22: 100000 cycle
connection mode
Remote control: tunnel type terminal 1 cable(s) 0.5…4 mm² rigid
Remote control: tunnel type terminal 1 cable(s) 0.5…4 mm² rigid with cable end
Remote control: tunnel type terminal 1 cable(s) 1...4 mm² flexible
Remote control: cage type terminal 1 cable(s) 1...4 mm² flexible with ferrule
Power circuit: cage type terminal 1 cable(s) 1.5...4 mm² rigid
Circuit circuit: tunnel type terminal 1 cable(s) 1.5…4 mm² rigid with cable end
Power circuit: tunnel type terminal 1 cable(s) 1.5…4 mm² flexible
Power circuit: terminal cage type 1 cable(s) 1.5...4 mm² flexible with cable end
width (w)
36 mm
network frequency
50/60 Hz
switching frequency
5 commutations/minute
100 commutations/jour
voltage indication
Indication ON/OFF
type of remote control
Illuminated push button 3 mA
wire stripping length
11 mm
depth
60 mm
mounting bracket
DIN rail
Network type
THAT
order type
Manual and remote control
Environment
degree of pollution
3
ip degree of protection
IP20 conforming to IEC 60529 (with opening)
IP40 conforming to IEC 60529 (enclosed)
product certificates
GOST
CCC
operating ambient temperature
-20…50 °C
standards
EN 669-1
EN 669-2-2
quality labels
KEMA
CEBEC
NF
VDE
IMQ
relative humidity
95% at 55°C
storage room temperature
-40…70 °C
sound pressure
60 dB
tropicalization
2