Main
composition of signaling contacts
1 "F"
[ithe] thermal current under enclosure
8 A
Range
VigiPacT
compatible current sensors
VigiPacT RMH monitoring relay
name of the device
RM12T
type of product or equipment
Multiplexer
charge minimum
10mA at 12V
service communication
Supervision via an internal bus
use of the relay
Monitoring relays
Complementary
9 mm pitches
12
[un] rated nominal voltage
220…240 V AC 50/60 Hz 70 to 110 %
Handle front plate colour
81 mm
tightening torque
0.5 Nm low auxiliary power supply:
0.5 Nm low earth leakage monitor:
0.5 Nm low detector:
0.5 Nm high detector:
product weight
0,42 kg
power consumed in va
8 VA
type of measurement
Internal earth fault current measurement, range: 80 to 100%, accuracy: +/- 10%
connection mode
Auxiliary power supply: screw terminal cable(s) 0.2...2.5 mm² flexible AWG 22...AWG 12
Auxiliary power supply: screw terminal cable(s) 0.2...2.5 mm² rigid AWG 22...AWG 12
Auxiliary power supply: screw terminal cable(s) 0.25...2.5 mm² flexible with cable end AWG 22...AWG 12
Earth leakage monitor: screw terminal cable(s) 0.2...2.5 mm² flexible AWG 22...AWG 12
Earth loss monitor: screw terminal cable(s) 0.2...2.5 mm² rigid AWG 22...AWG 12
Earth loss monitor: screw terminal cable(s) 0.25 …2.5 mm² flexible with cable end AWG 22...AWG 12
Detector: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12
Detector: screw terminal cable(s) 0.2…2 .5 mm² rigid AWG 22 to AWG 12
Detector: screw terminal cable(s) 0.25...2.5 mm² flexible with cable end AWG 22...AWG 12
width (w)
106 mm
mechanical robustness
Fire resistance conforming to IEC 60695-2-1
Protection IK 2 joules: IK07 conforming to EN 50102
Vibrations 13.2 to 100 Hz: 0.7 g
Vibrations 2 to 13.2 Hz: +/- 1 mm
surveillance
Electronics (continuous)
Power supply (continuous)
Relay/detector link (continuous)
RM12T detector/multiplexer and RM12T/RMH link (continuous)
function test
Local
wire stripping length
6 mm for bottom auxiliary power supply connection:
6 mm for bottom earth loss monitor connection:
6 mm for bottom detector connection:
6 mm for top detector connection:
depth
73,5 mm
mounting bracket
DIN rail
Environment
degree of pollution
3 conforming to IEC 60664-1
ip degree of protection
IP40 on front face: conforming to EN/IEC 60529
IP30 on sides: conforming to EN/IEC 60529
IP20 on connection terminals: conforming to EN/IEC 60529
electromagnetic compatibility
Conducted and radiated emissions: ,B conforming to CISPR 11 Conducted
radio frequency immunity test: ,3 conforming to IEC 61000-4-6
Electrostatic discharge immunity test: ,4 conforming to IEC 6100 -4-11
Disturbance transmitted by conduction at high energy: ,4 conforming to IEC 61000-4-5
Disturbance transmitted by conduction at low energy: ,4 conforming to IEC 61000-4-4
Radiated disturbance: ,3 conforming to IEC 61000-4-3
operating ambient temperature
-25…55 °C
overvoltage category
IV
relative humidity
95% at 55°C
shock resistance ik
IK07 conforming to EN 50102
storage room temperature
-40…85 °C